Restaurant coolroom and freezer room, each on its own condensing unit
An illustrative walk-in coolroom (1.73 kW at 2 °C) and freezer room (1.36 kW at −18 °C) behind a Melbourne restaurant, each on its own R-454C air-cooled condensing unit — carried through Kelvin from heat load to issued report. Every figure below is Kelvin’s own calculation — its engine run on the brief — and none is typed in.
Published , updated by Sentoro Technologies.
An illustrative design brief
This is a representative brief written to show the method, not a customer’s project, and every figure must be verified by a qualified professional before it’s relied on for a real one.
- Coolroom
- 1.73 kWat 2 °C
- Freezer room
- 1.36 kWat −18 °C
- Air on
- 34.8 °CMelbourne
- Refrigerant
- R-454CA2L · GWP 145 (AR4)
- Charge
- 2.4 kgpipework and receivers
- Energy
- 14.0 MWh/yrupper bound, both units
1The brief
A 120-seat restaurant. Its coolroom and freezer room stand side by side behind the kitchen, sharing one wall, each with a hinged door to the back-of-house corridor, and a condensing unit each in the yard behind. What follows is the whole brief as it is entered in Kelvin; everything after it is Kelvin’s calculation.
Design inputs
| Reading | Value |
|---|---|
| SiteMelbourne's summer brings some of the hottest air-on temperatures an Australian condensing unit is designed for, and it is where many of the country's restaurant coolrooms are. | Melbourne |
| RefrigerantBoth systems | R-454C |
| Design air onASHRAE 0.4 % annual cooling design dry bulb for Melbourne (ASHRAE 2013), as published in AIRAH Ecolibrium, June 2015, Table 2, the figure Kelvin's Melbourne climate profile is built from | 34.8°C |
| Condenser TDThe condenser's mean (its mid-glide: the dew and bubble points averaged) less the air entering it, at design | 10K |
| SuperheatAt the evaporator exit | 6K |
| SubcoolingAt the condenser exit | 3K |
| Compressor isentropic efficiencyOne figure for each compressor, as Kelvin's cycle takes it | 0.65 |
| Back-of-house airOn the rooms' outer walls and doors | 30°C |
| Ceiling spaceAbove the rooms' ceilings | 35°C |
The rooms
| Room | Size (m) | Room (°C) | Coil TD (K) | Product (kg/day) |
|---|---|---|---|---|
| Coolroom0.9 × 2 m Swing / personnel (North) · strip curtain · off-cycle defrost · 30 openings an hour | 4.2 × 3.0 × 2.4 | 2 | 6on the coil’s mean | 250in at 20 °C |
| Freezer room0.9 × 2 m Swing / personnel (North) · strip curtain · electric defrost · 10 openings an hour | 3.0 × 3.0 × 2.4 | −18 | 7on the coil’s mean | 80in at −12 °C |
Each unit cooler’s fan and the freezer’s defrost heater are entered, as Kelvin takes them, from the unit cooler’s datasheet; the brief’s figures are illustrative, not any maker’s.
The back of house, as the brief draws it
Point at a run or an evaporator to read it; tap to keep it. Zoom with the buttons (or Ctrl or ⌘ and the wheel), then drag the plan to move around it.
2Refrigerant and charge
Both systems run on R-454C, a blend of R-32 21.5 % / R-1234yf 78.5 % by mass: a low-GWP refrigerant a contractor can put in a new condensing unit today, and safety class A2L — lower toxicity, lower flammability. It is a zeotrope: at one pressure it boils and condenses over a range of temperatures (its glide), from its bubble point to its dew point. So this example states each heat exchanger’s temperature difference on a mean of that range — each unit cooler below its room, the condenser above the air — and gives each compressor duty at the dew points, as makers rate compressors for zeotropic blends. The coil’s mean is its inlet and dew point averaged; the condenser’s, its dew and bubble points averaged. Kelvin finds the pressure where each mean falls on R-454C’s own saturation data, the coil’s inlet from the cycle’s own liquid, and solves the cycle there (Design conditions). R-454C’s page has its pressure–temperature table and P–h diagram.
R-454C: GWP, ODP and safety class
| Reading | Value |
|---|---|
| Safety classLower toxicity, lower flammability. The class assigned in ISO 817 or ANSI/ASHRAE 34, as tabled in UNEP RTOC 2018; the Australian Government lists A2L (AS/NZS ISO 817). | A2L |
| GWP, 100-year (AR4)The mass-weighted sum of its components' figures from IPCC AR4 (2007): 21.5 % × 675 (R-32). R-1234yf has no AR4 figure and counts as zero, as in the Australian Government's figure. | 145 |
| GWP, 100-year (AR6)The mass-weighted sum of its components' figures from IPCC AR6 (2021): 21.5 % × 771 (R-32) + 78.5 % × 0.501 (R-1234yf). | 166 |
| ODPNone of its components is an ozone-depleting substance in the Montreal Protocol's annexes. | 0 |
An A2L refrigerant’s charge is limited by AS/NZS 5149: how much a circuit may hold depends on the room its refrigerant could leak into and on who occupies the building. Kelvin doesn’t make that check. What it gives the engineer who does is each circuit’s charge in the pipework it sized and the receiver, and the volume of each room its evaporator sits in:
What the charge check starts from
| Circuit | Charge (kg) | Room volume (m³) |
|---|---|---|
| CoolroomPipework and receiver | 1.16 | 30.2 |
| Freezer roomPipework and receiver | 1.20 | 21.6 |
Not in these figures: the charge in each unit cooler’s coil, and in the condensing unit’s own condenser and the piping inside its casing, which Kelvin has no volume for. Take them from the makers’ data and add them before checking a circuit against the standard.
3Heat load
Kelvin’s heat load engine sizes each room: transmission through its six surfaces, infiltration through its door, the day’s deliveries brought down to room temperature, and what the cook, the lights and the unit cooler’s fan add; the freezer adds its defrost heater. It takes the larger of holding and pull-down, adds a safety margin and spreads the day’s load over the hours the unit runs. Each room’s design load is the duty its condensing unit is selected for.
Room loads, by component
Each bar is a room’s loads over the day. The tick is its design load: the governing of holding and pull-down, plus a 10 % margin, spread over the hours the plant runs (16–18 h a day) — so a bar doesn’t sum to its tick.
Room loads
| Room | Transmission | Infiltration | Product | Internal | Defrost | Design |
|---|---|---|---|---|---|---|
| CoolroomChiller (MT), 2 °C · pulldown governs · 16 h/day | 0.322 | 0.363 | 0.196 | 0.167fans 0.120, 24 h/day | 0.000 | 1.73 |
| Freezer roomFreezer (LT), −18 °C · pulldown governs · 18 h/day | 0.348 | 0.339 | 0.012 | 0.146fans 0.112, 22.5 h/day | 0.083 | 1.36 |
Design load: the governing of holding and pull-down, plus a 10 % margin, scaled from 24 hours to the unit’s running hours (the Heat Load station’s default for each room type). The shared wall is taken against the other room’s temperature. Infiltration by the doorway method. Internal includes each unit cooler’s fan motor, whose heat goes into the room for the hours the fan runs, averaged over the day: the coolroom’s all day, the freezer’s all but its defrosts (Doors and defrost says why).
Coolroom plans
Design load 1.73 kW, pulldown governing. Point at a wall, the door or the unit to read its part of the load; tap to keep it.
4Doors and defrost
In a restaurant the door is the load that moves most. Kelvin works it by ASHRAE’s doorway method: the warm air that would pour through the opening with the door wide open, cut by the fraction of each hour it stands open, a flow factor, and how much of that flow the strip curtain stops. A 120-seat restaurant’s coolroom is opened every couple of minutes through service, so it is taken at the Heat Load station’s heavy traffic (30 openings an hour) and the freezer at medium (10); the engine counts that rate in every hour of the day, the quiet ones too.
Each door, as the heat load takes it
| Door | Openings (/h) | Open (% of hour) | Curtain stops | Wide open (kW) | Load (kW) |
|---|---|---|---|---|---|
| Coolroom0.9 × 2 m Swing / personnel (North), against 30 °C air | 30 | 8.3 | 85 % | 36.3 | 0.363 |
| Freezer room0.9 × 2 m Swing / personnel (North), against 30 °C air | 10 | 2.8 | 80 % | 76.2 | 0.339 |
Each opening holds the door for 10 s: Kelvin's assumption — ASHRAE R Ch. 24 gives no passage time for a personnel door. The curtain’s effectiveness is in service: E 0.85 for strip curtain on a doorway other than a freezer's — ASHRAE R Ch. 24 (2026), in service — 0.95 or higher newly installed, dropping with traffic and door maintenance to 0.8 on freezer doorways and about 0.85 on other doorways.
The coolroom’s design load again at each of the Heat Load station’s traffic levels, with its strip curtain and with none — the heat load engine run once for each:
Coolroom: design load by door traffic
| Traffic | Strip curtain | None |
|---|---|---|
| Light traffic4 openings an hour | 1.21door 0.05 | 1.66door 0.32 |
| Medium traffic10 openings an hour | 1.33door 0.12 | 2.46door 0.81 |
| Heavy traffic30 openings an hour | 1.73the brief · door 0.36 | 5.12door 2.42 |
A torn or tied-back curtain moves a room from the first column to the second; the condensing unit is selected for the first.
Defrost
| Reading | Value |
|---|---|
| Coolroom: off-cycleThe coil clears while the compressor is off: no heater, so no defrost load; the room's day is spread over 16 running hours | None |
| Freezer room: electricInto the room, averaged over the day: 1.5 kW × 80 min/day ÷ 1440 min | 0.083kW |
| Freezer room: heater energyFrom the energy analysis: the heater's rating for its minutes each day | 730kWh/yr |
| Coolroom: unit cooler fansAn off-cycle defrost clears the coil on room air, so the fans keep running while the compressor is off: their heat is counted all day in the heat load (0.120 kW, averaged), and their energy all day in the energy analysis (1,051 kWh a year), apart from the compressor's 16 hours | 24h/day |
| Freezer room: unit cooler fansThe fans stop only for each of the 4 defrosts and about 2.5 minutes after it, while the coil pulls down before it blows: their heat counted for those hours in the heat load (0.112 kW, averaged), their energy in the energy analysis (986 kWh a year), beyond the unit's 18 running hours | 22.5h/day |
5Design conditions
Each condensing unit is selected at the air it must work in on a hot Melbourne afternoon: 34.8 °C on the condenser, ASHRAE 0.4 % annual cooling design dry bulb for Melbourne (ASHRAE 2013), as published in AIRAH Ecolibrium, June 2015, Table 2, the figure Kelvin's Melbourne climate profile is built from. The coil’s mean is its inlet and dew point averaged; the condenser’s, its dew and bubble points averaged (its mid-glide). The inlet is the condenser’s liquid, at the brief’s subcooling, flashed to the evaporating pressure, so Kelvin solves that pressure for the coil’s mean on R-454C’s saturation data and the cycle’s own liquid, and finds the condensing pressure whose dew and bubble points average to the condenser’s. It solves the cycle at them, the evaporating temperature at its dew point and the condensing at its bubble point, as its cycle takes a zeotrope’s. The energy analysis runs each month at Melbourne’s design-high dry bulb for that month, the condensing bubble point the same 6.7 K above the air as at design, and never below 20 °C, where head pressure control holds it.
Melbourne, month by month
Each Navy Ink point is a month’s design high, not its mean. The tick on the scale is the design ambient the cycle is solved at, 34.8 °C.
Saturation temperatures at design
| Pressure | Dew | Mid-glide | Bubble | Coil inlet |
|---|---|---|---|---|
| Coolroom evaporatingCoil TD 6 K · coil mean −4.0 °C · 431.6 kPa abs | −1.5 | −5.4 | −9.3 | −6.5 |
| Freezer room evaporatingCoil TD 7 K · coil mean −25.0 °C · 194.4 kPa abs | −22.9 | −26.8 | −30.7 | −27.1 |
| Condensing, both units10 K above the air, on the mid-glide · 1,785.6 kPa abs | 48.1 | 44.8 | 41.5 | — |
The dew points are what the compressors are rated at (Condensing unit duties). The coil inlet is the expansion valve’s exit (state 4): the flash as the liquid drops to the evaporating pressure puts it above the bubble point, so the refrigerant in the coil runs from there to the dew point, and the coil’s mean, inlet to dew, is −4.0 °C in the coolroom and −25.0 °C in the freezer room, each room less its coil TD. Lowest condensing 20 °C, a bubble point, in the energy analysis.
6The two cycles
Each room has its own cycle, solved by Kelvin at the design air on, at the pressures Design conditions found: evaporating where the coil’s mean sits its TD below the room, condensing where the condenser’s mid-glide sits its TD above the air. Both are drawn on R-454C’s pressure–enthalpy diagram, the coolroom’s points marked C and the freezer’s F; point anywhere on it to read the state there.
The two cycles on R-454C's P–h diagram
Point anywhere on the diagram to read the state there
- Pressure
- —
- Temperature
- —
- Specific enthalpy
- —
- Specific entropy
- —
- Density
- —
- Specific volume
- —
- Saturation
- —
- Superheat or subcooling
- —
The points and lines are Kelvin’s design results; the dome, isotherms and the readout under the diagram are R-454C’s public diagram, computed with CoolProp.
Coolroom: state points
| Point | P (kPa) | T (°C) | h (kJ/kg) |
|---|---|---|---|
| C1Evaporator exit (superheated vapour) | 431.6 | 4.5 | 394.1 |
| C2Compressor discharge | 1,785.6 | 75.3 | 445.1 |
| C3Condenser exit (liquid, 3.0 K subcooled) | 1,785.6 | 38.5 | 258.0 |
| C4Expansion valve exit (two-phase) | 431.6 | −6.5 | 258.0 |
Point C1 is the dew point, −1.5 °C, plus 6 K of superheat, and C3 the bubble point, 41.5 °C, less 3 K of subcooling. Point C4, the coil’s inlet, is printed at its own two-phase temperature, between the evaporating bubble point (−9.3 °C) and the dew point. Point C2 is the state the discharge enthalpy sits at, on R-454C’s saturated vapour carried into superheat; the diagram’s readout at the same pressure and enthalpy agrees to within a kelvin. Enthalpy on the IIR datum.
Freezer room: state points
| Point | P (kPa) | T (°C) | h (kJ/kg) |
|---|---|---|---|
| F1Evaporator exit (superheated vapour) | 194.4 | −16.9 | 380.9 |
| F2Compressor discharge | 1,785.6 | 89.2 | 461.3 |
| F3Condenser exit (liquid, 3.0 K subcooled) | 1,785.6 | 38.5 | 258.0 |
| F4Expansion valve exit (two-phase) | 194.4 | −27.1 | 258.0 |
Point F1 is the dew point, −22.9 °C, plus 6 K of superheat, and F3 the bubble point, 41.5 °C, less 3 K of subcooling. Point F4, the coil’s inlet, is printed at its own two-phase temperature, between the evaporating bubble point (−30.7 °C) and the dew point. Point F2 is the state the discharge enthalpy sits at, on R-454C’s saturated vapour carried into superheat; the diagram’s readout at the same pressure and enthalpy agrees to within a kelvin. Enthalpy on the IIR datum.
7Condensing unit duties
What each condensing unit must do, at the design air on: the capacity at its evaporating temperature, the power its compressor draws for it, and the heat its condenser rejects. Each is stated at the dew points, suction and discharge, as makers rate compressors for zeotropic blends, so the figures read straight against a maker’s table. They are duties, not a model: the equipment catalogues are the engineer’s own, so the unit is chosen from a maker’s selection data against these figures. Brand-neutral.
Coolroom unit
| Reading | Value |
|---|---|
| Refrigeration capacityThe room's design load | 1.73kW |
| Suction, dew pointEvaporating; its mid-glide −5.4 °C, its bubble point −9.3 °C, the coil's mean −4.0 °C | −1.5°C |
| Discharge, dew pointCondensing; its mid-glide 44.8 °C, its bubble point 41.5 °C, where the 3 K of subcooling is counted from | 48.1°C |
| Compressor shaft power | 0.65kW |
| Heat rejectedCapacity plus shaft power | 2.38kW |
| COPThe Carnot COP between the same temperatures is 6.32 | 2.67 |
| Mass flow | 45.8kg/h |
| Swept volumeAt a volumetric efficiency of 0.86 | 2.78m³/h |
| Pressure ratio | 4.1 |
| Discharge temperatureThe state the discharge enthalpy sits at; the P–h diagram agrees at this point (The two cycles) | 75.3°C |
The unit cooler carries the same 1.73 kW at a 6 K TD on the coil’s mean (−4.0 °C), its liquid entering at −6.5 °C; the expansion valve’s duty is the same capacity between these pressures. Kelvin lists both duties for the makers’ selection; it doesn’t size either.
Freezer room unit
| Reading | Value |
|---|---|
| Refrigeration capacityThe room's design load | 1.36kW |
| Suction, dew pointEvaporating; its mid-glide −26.8 °C, its bubble point −30.7 °C, the coil's mean −25.0 °C | −22.9°C |
| Discharge, dew pointCondensing; its mid-glide 44.8 °C, its bubble point 41.5 °C, where the 3 K of subcooling is counted from | 48.1°C |
| Compressor shaft power | 0.89kW |
| Heat rejectedCapacity plus shaft power | 2.25kW |
| COPThe Carnot COP between the same temperatures is 3.89 | 1.53 |
| Mass flow | 39.8kg/h |
| Swept volumeAt a volumetric efficiency of 0.63 | 7.10m³/h |
| Pressure ratio | 9.2 |
| Discharge temperatureThe state the discharge enthalpy sits at; the P–h diagram agrees at this point (The two cycles) | 89.2°C |
The unit cooler carries the same 1.36 kW at a 7 K TD on the coil’s mean (−25.0 °C), its liquid entering at −27.1 °C; the expansion valve’s duty is the same capacity between these pressures. Kelvin lists both duties for the makers’ selection; it doesn’t size either.
A condensing unit and its room, part by part
8Pipe sizing
Each system’s suction and liquid lines run from its condensing unit in the yard, through the building’s wall and along the corridor in the ceiling space, and drop to its unit cooler. Kelvin sizes each line to its velocity band on its own flow — the Pipe Layout station’s default — and reports what each loses in saturation temperature.
Pipe layout
Point at a run or an evaporator to read it; tap to keep it. Zoom with the buttons (or Ctrl or ⌘ and the wheel), then drag the plan to move around it. Each run's size is in its tooltip, or on the plan with “Sizes on the plan”.
Coolroom: field lines
| Line | Size | v (m/s) | Δp (kPa) | ΔT (K) |
|---|---|---|---|---|
| Suction8.7 m · ok | 1/2" | 7.30 | 9.93 | 0.68 |
| Liquid8.7 m · ok | 1/4" | 0.71 | 14.14 | 0.34 |
Suction path 0.68 K (9.9 kPa); liquid path 0.34 K (14.1 kPa), the liquid keeping its 3.0 K of subcooling to the valve.
Freezer room: field lines
| Line | Size | v (m/s) | Δp (kPa) | ΔT (K) |
|---|---|---|---|---|
| Suction10.8 m · ok | 3/4" | 5.66 | 2.43 | 0.31 |
| Liquid10.8 m · ok | 1/4" | 0.61 | 13.70 | 0.33 |
Suction path 0.31 K (2.4 kPa); liquid path 0.33 K (13.7 kPa), the liquid keeping its 3.0 K of subcooling to the valve.
Velocity bands: ASHRAE Handbook—Refrigeration Ch.1 velocity practice (suction 4.5–20, discharge 10–18, liquid 0.5–1.25 m/s). The plan marks each run as the Pipe Layout station would: the coolroom's suction line loses more than half a kelvin, which it marks as a moderate impact on the compressor (a threshold of Kelvin’s sizing code, not a cited figure). The condensing unit’s own lines, its discharge and its condenser to receiver, are inside its casing: they are given no length here, and their sizes and charge are its maker’s.
9Refrigerant charge
Each circuit’s charge in what Kelvin sized: every line at its own density, and the receiver at its liquid level. On condensing units this size most of it is in the receiver; the coil and the unit’s condenser hold the rest, from the makers’ data.
Coolroom: where the charge is
Freezer room: where the charge is
Charge
| Circuit | Pipework | Receiver | Total |
|---|---|---|---|
| Coolroom2 lines, 0.97 L · receiver 2.5 L at 40 % liquid | 0.17 | 0.98 | 1.16 |
| Freezer room2 lines, 2.62 L · receiver 2.5 L at 40 % liquid | 0.22 | 0.98 | 1.20 |
| Both circuits | 0.39 | 1.97 | 2.35kg |
10Energy and running cost
Each unit month by month: its cycle re-solved at the month’s design-high air, its compressor and condenser fan running the hours a day its room’s load was spread over, its unit cooler’s fans their own hours (Doors and defrost) and, for the freezer, its defrost heater, at 28 c/kWh. Upper bound at design-high ambients: every hour of each month is run at that month's design dry bulb, not its mean, so expected consumption is lower.
Coolroom unit, monthly energy
Freezer room unit, monthly energy
A year
| Unit | Compressor | Fans | Defrost | Total (kWh) | Cost |
|---|---|---|---|---|---|
| Coolroomcompressor 16 h/day · unit cooler fans 24 h/day · average COP 3.63 | 3,405 | 2,102 | 0 | 5,507 | $1,542 |
| Freezer roomcompressor 18 h/day · unit cooler fans 22.5 h/day · average COP 1.94 | 5,547 | 2,168 | 730 | 8,445 | $2,365 |
| Both units | 13,952 | $3,907 |
Running cost
| Reading | Value |
|---|---|
| Coolroom unit, a yearEnergy $1,542 and 0.06 kg of refrigerant topped up at $60/kg ($3), at 5 % of its charge a year | $1,545 |
| Freezer room unit, a yearEnergy $2,365 and 0.06 kg of refrigerant topped up at $60/kg ($4), at 5 % of its charge a year | $2,368 |
| Both units over 10 yearsUndiscounted, at today's tariff and refrigerant price | $39,136 |
11The issued report
In Kelvin each stage above is a station with its own record, and each record issues as a PDF report with its inputs, results and sources. Two condensing units are two designs, so each issues its own set:
The chain, and what each station issues
What Kelvin issues
| Report | Sections |
|---|---|
| Heat load report | Room schedule · Suction group totals |
| Cycle report | Input parameters · Cycle state points · System schematic · Engineering checks |
| Pipe layout report | Floor plan · Pipe schedule · Sizing checks · Evaporator performance |
| Equipment schedule | Compressors · Condenser / gas cooler · Evaporators · Expansion valves · Liquid receiver |
| Refrigerant charge report | Charge split · Pipe charge breakdown · Receiver and oil · Liquid line pressure drop |
| Energy report | Analysis inputs · Monthly energy · Monthly breakdown |
| Running cost report | Inputs and assumptions · Running cost · Pipework BOM |
Another worked example
- Transcritical CO₂ supermarket pack, cycle to issued report
An illustrative transcritical CO₂ booster pack for a Brisbane supermarket — 117 kW medium temperature at −8 °C and 31 kW low temperature at −30 °C — carried through Kelvin from heat load to issued report.
Put your own rooms through Kelvin
Kelvin’s Free plan includes the refrigerant library, P–h diagrams, single-stage cycles and draft reports. Paid plans carry a system on through pipework, equipment, charge, energy and cost to issued reports.
Verify before relying on these figures
Kelvin’s calculations are design aids based on published methods and standard thermodynamic and hydraulic models. Every figure on this page must be verified by a qualified professional before it’s relied on, and a real design checked against AS/NZS 5149 and the equipment makers’ data.