Restaurant coolroom and freezer room, each on its own condensing unit

An illustrative walk-in coolroom (1.73 kW at 2 °C) and freezer room (1.36 kW at −18 °C) behind a Melbourne restaurant, each on its own R-454C air-cooled condensing unit — carried through Kelvin from heat load to issued report. Every figure below is Kelvin’s own calculation — its engine run on the brief — and none is typed in.

Published , updated by Sentoro Technologies.

Note

An illustrative design brief

This is a representative brief written to show the method, not a customer’s project, and every figure must be verified by a qualified professional before it’s relied on for a real one.

Coolroom
1.73 kWat 2 °C
Freezer room
1.36 kWat −18 °C
Air on
34.8 °CMelbourne
Refrigerant
R-454CA2L · GWP 145 (AR4)
Charge
2.4 kgpipework and receivers
Energy
14.0 MWh/yrupper bound, both units

1The brief

A 120-seat restaurant. Its coolroom and freezer room stand side by side behind the kitchen, sharing one wall, each with a hinged door to the back-of-house corridor, and a condensing unit each in the yard behind. What follows is the whole brief as it is entered in Kelvin; everything after it is Kelvin’s calculation.

Design inputs

The brief's design inputs
ReadingValue
SiteMelbourne's summer brings some of the hottest air-on temperatures an Australian condensing unit is designed for, and it is where many of the country's restaurant coolrooms are.Melbourne
RefrigerantBoth systemsR-454C
Design air onASHRAE 0.4 % annual cooling design dry bulb for Melbourne (ASHRAE 2013), as published in AIRAH Ecolibrium, June 2015, Table 2, the figure Kelvin's Melbourne climate profile is built from34.8°C
Condenser TDThe condenser's mean (its mid-glide: the dew and bubble points averaged) less the air entering it, at design10K
SuperheatAt the evaporator exit6K
SubcoolingAt the condenser exit3K
Compressor isentropic efficiencyOne figure for each compressor, as Kelvin's cycle takes it0.65
Back-of-house airOn the rooms' outer walls and doors30°C
Ceiling spaceAbove the rooms' ceilings35°C

The rooms

as entered
The two rooms as the brief enters them
RoomSize (m)Room (°C)Coil TD (K)Product (kg/day)
Coolroom0.9 × 2 m Swing / personnel (North) · strip curtain · off-cycle defrost · 30 openings an hour4.2 × 3.0 × 2.426on the coil’s mean250in at 20 °C
Freezer room0.9 × 2 m Swing / personnel (North) · strip curtain · electric defrost · 10 openings an hour3.0 × 3.0 × 2.4−187on the coil’s mean80in at −12 °C

Each unit cooler’s fan and the freezer’s defrost heater are entered, as Kelvin takes them, from the unit cooler’s datasheet; the brief’s figures are illustrative, not any maker’s.

The back of house, as the brief draws it

2 evaporators · 2 runs
The pipe layout on Kelvin’s Pipe Layout canvas, read only: each suction and liquid run labelled with its size. Point at a run or an evaporator for its figures; the governing paths and the pack’s own lines are in the tables below.

Point at a run or an evaporator to read it; tap to keep it. Zoom with the buttons (or Ctrl or ⌘ and the wheel), then drag the plan to move around it.

2Refrigerant and charge

Both systems run on R-454C, a blend of R-32 21.5 % / R-1234yf 78.5 % by mass: a low-GWP refrigerant a contractor can put in a new condensing unit today, and safety class A2L — lower toxicity, lower flammability. It is a zeotrope: at one pressure it boils and condenses over a range of temperatures (its glide), from its bubble point to its dew point. So this example states each heat exchanger’s temperature difference on a mean of that range — each unit cooler below its room, the condenser above the air — and gives each compressor duty at the dew points, as makers rate compressors for zeotropic blends. The coil’s mean is its inlet and dew point averaged; the condenser’s, its dew and bubble points averaged. Kelvin finds the pressure where each mean falls on R-454C’s own saturation data, the coil’s inlet from the cycle’s own liquid, and solves the cycle there (Design conditions). R-454C’s page has its pressure–temperature table and P–h diagram.

R-454C: GWP, ODP and safety class

R-454C's GWP, ODP and safety class, with their sources
ReadingValue
Safety classLower toxicity, lower flammability. The class assigned in ISO 817 or ANSI/ASHRAE 34, as tabled in UNEP RTOC 2018; the Australian Government lists A2L (AS/NZS ISO 817).A2L
GWP, 100-year (AR4)The mass-weighted sum of its components' figures from IPCC AR4 (2007): 21.5 % × 675 (R-32). R-1234yf has no AR4 figure and counts as zero, as in the Australian Government's figure.145
GWP, 100-year (AR6)The mass-weighted sum of its components' figures from IPCC AR6 (2021): 21.5 % × 771 (R-32) + 78.5 % × 0.501 (R-1234yf).166
ODPNone of its components is an ozone-depleting substance in the Montreal Protocol's annexes.0

An A2L refrigerant’s charge is limited by AS/NZS 5149: how much a circuit may hold depends on the room its refrigerant could leak into and on who occupies the building. Kelvin doesn’t make that check. What it gives the engineer who does is each circuit’s charge in the pipework it sized and the receiver, and the volume of each room its evaporator sits in:

What the charge check starts from

per circuit
Each circuit's charge as Kelvin works it out, and the room its evaporator is in
CircuitCharge (kg)Room volume (m³)
CoolroomPipework and receiver1.1630.2
Freezer roomPipework and receiver1.2021.6

Not in these figures: the charge in each unit cooler’s coil, and in the condensing unit’s own condenser and the piping inside its casing, which Kelvin has no volume for. Take them from the makers’ data and add them before checking a circuit against the standard.

3Heat load

Kelvin’s heat load engine sizes each room: transmission through its six surfaces, infiltration through its door, the day’s deliveries brought down to room temperature, and what the cook, the lights and the unit cooler’s fan add; the freezer adds its defrost heater. It takes the larger of holding and pull-down, adds a safety margin and spreads the day’s load over the hours the unit runs. Each room’s design load is the duty its condensing unit is selected for.

Room loads, by component

kW
Each coolroom’s loads as a stacked bar, with its design load marked as a tick. The exact values are in the table on this page.
Load (kW)TransmissionInfiltrationProductInternalDefrostDesign load
Coolroom
design 1.73 kW
Freezer room
design 1.36 kW

Each bar is a room’s loads over the day. The tick is its design load: the governing of holding and pull-down, plus a 10 % margin, spread over the hours the plant runs (16–18 h a day) — so a bar doesn’t sum to its tick.

Room loads

kW
The two rooms' heat loads
RoomTrans­missionInfil­trationProductInternalDefrostDesign
CoolroomChiller (MT), 2 °C · pulldown governs · 16 h/day0.3220.3630.1960.167fans 0.120, 24 h/day0.0001.73
Freezer roomFreezer (LT), −18 °C · pulldown governs · 18 h/day0.3480.3390.0120.146fans 0.112, 22.5 h/day0.0831.36

Design load: the governing of holding and pull-down, plus a 10 % margin, scaled from 24 hours to the unit’s running hours (the Heat Load station’s default for each room type). The shared wall is taken against the other room’s temperature. Infiltration by the doorway method. Internal includes each unit cooler’s fan motor, whose heat goes into the room for the hours the fan runs, averaged over the day: the coolroom’s all day, the freezer’s all but its defrosts (Doors and defrost says why).

Coolroom plans

4.2 × 3.0 m · 2.4 m high · 2 °C
Room
Coolroom on Kelvin’s Heat Load room plan, read only: its walls, door and unit. Point at a wall, the door or the unit for its part of the load; the room table above carries every figure.

Design load 1.73 kW, pulldown governing. Point at a wall, the door or the unit to read its part of the load; tap to keep it.

4Doors and defrost

In a restaurant the door is the load that moves most. Kelvin works it by ASHRAE’s doorway method: the warm air that would pour through the opening with the door wide open, cut by the fraction of each hour it stands open, a flow factor, and how much of that flow the strip curtain stops. A 120-seat restaurant’s coolroom is opened every couple of minutes through service, so it is taken at the Heat Load station’s heavy traffic (30 openings an hour) and the freezer at medium (10); the engine counts that rate in every hour of the day, the quiet ones too.

Each door, as the heat load takes it

Each room's door and its infiltration
DoorOpenings (/h)Open (% of hour)Curtain stopsWide open (kW)Load (kW)
Coolroom0.9 × 2 m Swing / personnel (North), against 30 °C air308.385 %36.30.363
Freezer room0.9 × 2 m Swing / personnel (North), against 30 °C air102.880 %76.20.339

Each opening holds the door for 10 s: Kelvin's assumption — ASHRAE R Ch. 24 gives no passage time for a personnel door. The curtain’s effectiveness is in service: E 0.85 for strip curtain on a doorway other than a freezer's — ASHRAE R Ch. 24 (2026), in service — 0.95 or higher newly installed, dropping with traffic and door maintenance to 0.8 on freezer doorways and about 0.85 on other doorways.

The coolroom’s design load again at each of the Heat Load station’s traffic levels, with its strip curtain and with none — the heat load engine run once for each:

Coolroom: design load by door traffic

kW
The coolroom's design load at each door traffic level, with and without its strip curtain
TrafficStrip curtainNone
Light traffic4 openings an hour1.21door 0.051.66door 0.32
Medium traffic10 openings an hour1.33door 0.122.46door 0.81
Heavy traffic30 openings an hour1.73the brief · door 0.365.12door 2.42

A torn or tied-back curtain moves a room from the first column to the second; the condensing unit is selected for the first.

Defrost

How each room's coil is defrosted, and what it costs
ReadingValue
Coolroom: off-cycleThe coil clears while the compressor is off: no heater, so no defrost load; the room's day is spread over 16 running hoursNone
Freezer room: electricInto the room, averaged over the day: 1.5 kW × 80 min/day ÷ 1440 min0.083kW
Freezer room: heater energyFrom the energy analysis: the heater's rating for its minutes each day730kWh/yr
Coolroom: unit cooler fansAn off-cycle defrost clears the coil on room air, so the fans keep running while the compressor is off: their heat is counted all day in the heat load (0.120 kW, averaged), and their energy all day in the energy analysis (1,051 kWh a year), apart from the compressor's 16 hours24h/day
Freezer room: unit cooler fansThe fans stop only for each of the 4 defrosts and about 2.5 minutes after it, while the coil pulls down before it blows: their heat counted for those hours in the heat load (0.112 kW, averaged), their energy in the energy analysis (986 kWh a year), beyond the unit's 18 running hours22.5h/day

5Design conditions

Each condensing unit is selected at the air it must work in on a hot Melbourne afternoon: 34.8 °C on the condenser, ASHRAE 0.4 % annual cooling design dry bulb for Melbourne (ASHRAE 2013), as published in AIRAH Ecolibrium, June 2015, Table 2, the figure Kelvin's Melbourne climate profile is built from. The coil’s mean is its inlet and dew point averaged; the condenser’s, its dew and bubble points averaged (its mid-glide). The inlet is the condenser’s liquid, at the brief’s subcooling, flashed to the evaporating pressure, so Kelvin solves that pressure for the coil’s mean on R-454C’s saturation data and the cycle’s own liquid, and finds the condensing pressure whose dew and bubble points average to the condenser’s. It solves the cycle at them, the evaporating temperature at its dew point and the condensing at its bubble point, as its cycle takes a zeotrope’s. The energy analysis runs each month at Melbourne’s design-high dry bulb for that month, the condensing bubble point the same 6.7 K above the air as at design, and never below 20 °C, where head pressure control holds it.

Melbourne, month by month

°C
Melbourne’s monthly design dry bulbs as a line and the design ambient marked on the scale. The exact values are in the table on this page.
Design dry bulb (°C)Design dry bulbDesign ambient 34.8 °C

Each Navy Ink point is a month’s design high, not its mean. The tick on the scale is the design ambient the cycle is solved at, 34.8 °C.

Saturation temperatures at design

°C · 34.8 °C air on
Each pressure's dew, mid-glide and bubble points at design, and the temperature at each coil's inlet
PressureDewMid-glideBubbleCoil inlet
Coolroom evaporatingCoil TD 6 K · coil mean −4.0 °C · 431.6 kPa abs−1.5−5.4−9.3−6.5
Freezer room evaporatingCoil TD 7 K · coil mean −25.0 °C · 194.4 kPa abs−22.9−26.8−30.7−27.1
Condensing, both units10 K above the air, on the mid-glide · 1,785.6 kPa abs48.144.841.5—

The dew points are what the compressors are rated at (Condensing unit duties). The coil inlet is the expansion valve’s exit (state 4): the flash as the liquid drops to the evaporating pressure puts it above the bubble point, so the refrigerant in the coil runs from there to the dew point, and the coil’s mean, inlet to dew, is −4.0 °C in the coolroom and −25.0 °C in the freezer room, each room less its coil TD. Lowest condensing 20 °C, a bubble point, in the energy analysis.

6The two cycles

Each room has its own cycle, solved by Kelvin at the design air on, at the pressures Design conditions found: evaporating where the coil’s mean sits its TD below the room, condensing where the condenser’s mid-glide sits its TD above the air. Both are drawn on R-454C’s pressure–enthalpy diagram, the coolroom’s points marked C and the freezer’s F; point anywhere on it to read the state there.

The two cycles on R-454C's P–h diagram

log P · h
Pressure (kPa abs)
Specific enthalpy (kJ/kg)

Point anywhere on the diagram to read the state there

Pressure
—
Temperature
—
Specific enthalpy
—
Specific entropy
—
Density
—
Specific volume
—
Saturation
—
Superheat or subcooling
—

The points and lines are Kelvin’s design results; the dome, isotherms and the readout under the diagram are R-454C’s public diagram, computed with CoolProp.

Coolroom: state points

kPa abs · °C · kJ/kg
The coolroom cycle's state points
PointP (kPa)T (°C)h (kJ/kg)
C1Evaporator exit (superheated vapour)431.64.5394.1
C2Compressor discharge1,785.675.3445.1
C3Condenser exit (liquid, 3.0 K subcooled)1,785.638.5258.0
C4Expansion valve exit (two-phase)431.6−6.5258.0

Point C1 is the dew point, −1.5 °C, plus 6 K of superheat, and C3 the bubble point, 41.5 °C, less 3 K of subcooling. Point C4, the coil’s inlet, is printed at its own two-phase temperature, between the evaporating bubble point (−9.3 °C) and the dew point. Point C2 is the state the discharge enthalpy sits at, on R-454C’s saturated vapour carried into superheat; the diagram’s readout at the same pressure and enthalpy agrees to within a kelvin. Enthalpy on the IIR datum.

Freezer room: state points

kPa abs · °C · kJ/kg
The freezer room cycle's state points
PointP (kPa)T (°C)h (kJ/kg)
F1Evaporator exit (superheated vapour)194.4−16.9380.9
F2Compressor discharge1,785.689.2461.3
F3Condenser exit (liquid, 3.0 K subcooled)1,785.638.5258.0
F4Expansion valve exit (two-phase)194.4−27.1258.0

Point F1 is the dew point, −22.9 °C, plus 6 K of superheat, and F3 the bubble point, 41.5 °C, less 3 K of subcooling. Point F4, the coil’s inlet, is printed at its own two-phase temperature, between the evaporating bubble point (−30.7 °C) and the dew point. Point F2 is the state the discharge enthalpy sits at, on R-454C’s saturated vapour carried into superheat; the diagram’s readout at the same pressure and enthalpy agrees to within a kelvin. Enthalpy on the IIR datum.

7Condensing unit duties

What each condensing unit must do, at the design air on: the capacity at its evaporating temperature, the power its compressor draws for it, and the heat its condenser rejects. Each is stated at the dew points, suction and discharge, as makers rate compressors for zeotropic blends, so the figures read straight against a maker’s table. They are duties, not a model: the equipment catalogues are the engineer’s own, so the unit is chosen from a maker’s selection data against these figures. Brand-neutral.

Coolroom unit

at 34.8 °C air on
The coolroom condensing unit's duty
ReadingValue
Refrigeration capacityThe room's design load1.73kW
Suction, dew pointEvaporating; its mid-glide −5.4 °C, its bubble point −9.3 °C, the coil's mean −4.0 °C−1.5°C
Discharge, dew pointCondensing; its mid-glide 44.8 °C, its bubble point 41.5 °C, where the 3 K of subcooling is counted from48.1°C
Compressor shaft power0.65kW
Heat rejectedCapacity plus shaft power2.38kW
COPThe Carnot COP between the same temperatures is 6.322.67
Mass flow45.8kg/h
Swept volumeAt a volumetric efficiency of 0.862.78m³/h
Pressure ratio4.1
Discharge temperatureThe state the discharge enthalpy sits at; the P–h diagram agrees at this point (The two cycles)75.3°C

The unit cooler carries the same 1.73 kW at a 6 K TD on the coil’s mean (−4.0 °C), its liquid entering at −6.5 °C; the expansion valve’s duty is the same capacity between these pressures. Kelvin lists both duties for the makers’ selection; it doesn’t size either.

Freezer room unit

at 34.8 °C air on
The freezer room condensing unit's duty
ReadingValue
Refrigeration capacityThe room's design load1.36kW
Suction, dew pointEvaporating; its mid-glide −26.8 °C, its bubble point −30.7 °C, the coil's mean −25.0 °C−22.9°C
Discharge, dew pointCondensing; its mid-glide 44.8 °C, its bubble point 41.5 °C, where the 3 K of subcooling is counted from48.1°C
Compressor shaft power0.89kW
Heat rejectedCapacity plus shaft power2.25kW
COPThe Carnot COP between the same temperatures is 3.891.53
Mass flow39.8kg/h
Swept volumeAt a volumetric efficiency of 0.637.10m³/h
Pressure ratio9.2
Discharge temperatureThe state the discharge enthalpy sits at; the P–h diagram agrees at this point (The two cycles)89.2°C

The unit cooler carries the same 1.36 kW at a 7 K TD on the coil’s mean (−25.0 °C), its liquid entering at −27.1 °C; the expansion valve’s duty is the same capacity between these pressures. Kelvin lists both duties for the makers’ selection; it doesn’t size either.

A condensing unit and its room, part by part

Single Stage system schematic, not to scale: evaporator, compressor, condenser and expansion valve. Suction, discharge and liquid lines are each named. Point at, tap or tab to a component, line or valve to read its duty.

8Pipe sizing

Each system’s suction and liquid lines run from its condensing unit in the yard, through the building’s wall and along the corridor in the ceiling space, and drop to its unit cooler. Kelvin sizes each line to its velocity band on its own flow — the Pipe Layout station’s default — and reports what each loses in saturation temperature.

Pipe layout

2 evaporators · 4 segments drawn · 1 flagged
The pipe layout on Kelvin’s Pipe Layout canvas, read only: each suction and liquid run labelled with its size. Point at a run or an evaporator for its figures; the governing paths and the pack’s own lines are in the tables below.

Point at a run or an evaporator to read it; tap to keep it. Zoom with the buttons (or Ctrl or ⌘ and the wheel), then drag the plan to move around it. Each run's size is in its tooltip, or on the plan with “Sizes on the plan”.

Coolroom: field lines

velocity basis
The coolroom system's suction and liquid lines
LineSizev (m/s)Δp (kPa)ΔT (K)
Suction8.7 m · ok1/2"7.309.930.68
Liquid8.7 m · ok1/4"0.7114.140.34

Suction path 0.68 K (9.9 kPa); liquid path 0.34 K (14.1 kPa), the liquid keeping its 3.0 K of subcooling to the valve.

Freezer room: field lines

velocity basis
The freezer room system's suction and liquid lines
LineSizev (m/s)Δp (kPa)ΔT (K)
Suction10.8 m · ok3/4"5.662.430.31
Liquid10.8 m · ok1/4"0.6113.700.33

Suction path 0.31 K (2.4 kPa); liquid path 0.33 K (13.7 kPa), the liquid keeping its 3.0 K of subcooling to the valve.

Velocity bands: ASHRAE Handbook—Refrigeration Ch.1 velocity practice (suction 4.5–20, discharge 10–18, liquid 0.5–1.25 m/s). The plan marks each run as the Pipe Layout station would: the coolroom's suction line loses more than half a kelvin, which it marks as a moderate impact on the compressor (a threshold of Kelvin’s sizing code, not a cited figure). The condensing unit’s own lines, its discharge and its condenser to receiver, are inside its casing: they are given no length here, and their sizes and charge are its maker’s.

9Refrigerant charge

Each circuit’s charge in what Kelvin sized: every line at its own density, and the receiver at its liquid level. On condensing units this size most of it is in the receiver; the coil and the unit’s condenser hold the rest, from the makers’ data.

Coolroom: where the charge is

1.2 kg
The charge as one bar: the receiver, then the pipework by line type, each in proportion to its mass. The exact values are in the table on this page.
Charge (kg)

Freezer room: where the charge is

1.2 kg
The charge as one bar: the receiver, then the pipework by line type, each in proportion to its mass. The exact values are in the table on this page.
Charge (kg)

Charge

kg
Each circuit's charge
CircuitPipeworkReceiverTotal
Coolroom2 lines, 0.97 L · receiver 2.5 L at 40 % liquid0.170.981.16
Freezer room2 lines, 2.62 L · receiver 2.5 L at 40 % liquid0.220.981.20
Both circuits0.391.972.35kg

10Energy and running cost

Each unit month by month: its cycle re-solved at the month’s design-high air, its compressor and condenser fan running the hours a day its room’s load was spread over, its unit cooler’s fans their own hours (Doors and defrost) and, for the freezer, its defrost heater, at 28 c/kWh. Upper bound at design-high ambients: every hour of each month is run at that month's design dry bulb, not its mean, so expected consumption is lower.

Coolroom unit, monthly energy

5,507 kWh / yr
Each month's energy as bars — compressor, fans and any defrost — over the air on that drove it as a line. The exact values are in the table on this page.
Energy (kWh)Energy
Ambient (°C)

Freezer room unit, monthly energy

8,445 kWh / yr
Each month's energy as bars — compressor, fans and any defrost — over the air on that drove it as a line. The exact values are in the table on this page.
Energy (kWh)Energy
Ambient (°C)

A year

upper bound
Each unit's energy in a year, and its running cost
UnitCompressorFansDefrostTotal (kWh)Cost
Coolroomcompressor 16 h/day · unit cooler fans 24 h/day · average COP 3.633,4052,10205,507$1,542
Freezer roomcompressor 18 h/day · unit cooler fans 22.5 h/day · average COP 1.945,5472,1687308,445$2,365
Both units13,952$3,907

Running cost

10 years
Energy and refrigerant top-up, a year and over the period
ReadingValue
Coolroom unit, a yearEnergy $1,542 and 0.06 kg of refrigerant topped up at $60/kg ($3), at 5 % of its charge a year$1,545
Freezer room unit, a yearEnergy $2,365 and 0.06 kg of refrigerant topped up at $60/kg ($4), at 5 % of its charge a year$2,368
Both units over 10 yearsUndiscounted, at today's tariff and refrigerant price$39,136

11The issued report

In Kelvin each stage above is a station with its own record, and each record issues as a PDF report with its inputs, results and sources. Two condensing units are two designs, so each issues its own set:

The chain, and what each station issues

7 reports
Kelvin’s calculation chain, each station with the report it issues for this design. The reports and their sections are in the table below.
  1. 1Heat LoadHeat load report
  2. 2CycleCycle report
  3. 3Pipe LayoutPipe layout report
  4. 4EquipmentEquipment schedule
  5. 5Refrigerant ChargeRefrigerant charge report
  6. 6EnergyEnergy report
  7. 7BOM & Running CostRunning cost report

What Kelvin issues

for each unit
The reports Kelvin issues for each unit, and their sections
ReportSections
Heat load reportRoom schedule · Suction group totals
Cycle reportInput parameters · Cycle state points · System schematic · Engineering checks
Pipe layout reportFloor plan · Pipe schedule · Sizing checks · Evaporator performance
Equipment scheduleCompressors · Condenser / gas cooler · Evaporators · Expansion valves · Liquid receiver
Refrigerant charge reportCharge split · Pipe charge breakdown · Receiver and oil · Liquid line pressure drop
Energy reportAnalysis inputs · Monthly energy · Monthly breakdown
Running cost reportInputs and assumptions · Running cost · Pipework BOM

Another worked example

Put your own rooms through Kelvin

Kelvin’s Free plan includes the refrigerant library, P–h diagrams, single-stage cycles and draft reports. Paid plans carry a system on through pipework, equipment, charge, energy and cost to issued reports.

Note

Verify before relying on these figures

Kelvin’s calculations are design aids based on published methods and standard thermodynamic and hydraulic models. Every figure on this page must be verified by a qualified professional before it’s relied on, and a real design checked against AS/NZS 5149 and the equipment makers’ data.